DYLY-QT gas fire extinguishing system experimental platform

Release time:2024-06-20 02:30viewed:times
  • DYLY-QT gas fire extinguishing system experimental platform
I. Tr*ning device for gas fire extinguishing system Overview:
1. Basic principles and fire extinguishing methods:
According to the requirements of the specification, the system adopts two types of composition: a fully flooded unit independent system and a combined distribution system. The unit independent system is a form in which a set of fire extinguishing agent storage device corresponds to a set of pipe network system to protect a protection area. The combined system is a form in which a set of fire extinguishing agent storage device corresponds to several pipe network systems to protect two upper protection areas.
2. Tr*ning device for gas fire extinguishing system Composition:
Pipe network heptafluoropropane fire extinguishing device, pipe network, gas fire extinguishing controller, fire detector, sound and light alarm, gas discharge indicator light, emergency start and stop button, external power supply, etc. constitute a complete automatic fire extinguishing system.
II. Control mode: 
This system m*nly has four control modes: automatic, manual, mechanical emergency manual and emergency start/stop. 
(1) Automatic control mode: This fire extinguishing controller is equipped with a smoke fire detector and a fixed temperature heat fire detector. There is a control mode selection lock on the controller. When it is placed in the "automatic" position, the fire extinguishing controller is in the automatic control state. When only one detector sends out a fire signal, the controller will send out a fire alarm sound and light signal to notify that an abnormal situation has occurred, but will not start the fire extinguishing device to release the fire extinguishing agent. If it is necessary to start the fire extinguishing device to extinguish the fire, you can press the "emergency start button" to start the fire extinguishing device to release the fire extinguishing agent and implement fire extinguishing. When two detectors send out fire signals at the same time, the controller will send out fire sound and light signals to notify that a fire has occurred and that relevant personnel should evacuate the scene, and issue a linkage command to shut down linkage equipment such as fans and fire dampers. After a period of delay, it will issue a fire extinguishing command to open the solenoid valve, start the gas to open the cont*ner valve, release the fire extinguishing agent, and implement fire extinguishing. If it is found that the fire extinguishing device does not need to be started during the alarm process, you can press the "emergency stop button" outside the protection area or on the control operation panel to terminate the occurrence of the control fire extinguishing command, do not start the fire extinguishing device, release the fire extinguishing agent, and implement fire extinguishing. 
(2) Manual control mode: When the control mode selection lock on the controller is placed in the "manual" position, the fire extinguishing controller is in manual control. 
state. At this time, when the fire detector sends out a fire alarm signal, the controller will send out a fire sound and light alarm signal, but will not start the fire extinguishing device. After observation by personnel, when confirming that a fire has occurred, the "emergency start button" outside the protection zone or on the controller operation panel can be pressed to start the fire extinguishing device, release the fire extinguishing agent, and implement fire extinguishing. However, the alarm signal still exists. 
Regardless of whether the device is in automatic or manual state, pressing any emergency start button can start the fire extinguishing device, release the fire extinguishing agent, and implement fire extinguishing. At the same time, the controller immediately enters the fire extinguishing alarm state. 
(3) Emergency mechanical start working mode: used when the controller f*ls. When the on-duty personnel determine that it is a fire, they should immediately notify all personnel on the scene to evacuate the scene. After confirming that all personnel have evacuated the scene, the emergency mechanical start can be implemented according to the following steps: ① Manually close the linkage equipment and cut off the power supply. ② Open the corresponding protection zone selection valve. ③ Open the cont*ner valve on the corresponding protection zone storage bottle group in groups or one by one to immediately implement fire extinguishing. 
(4) Emergency start/stop working mode: used in emergency situations. In the first case, when the on-duty personnel discovers a fire and the gas fire extinguishing controller does not send out an audible or visual alarm signal, they should immediately notify all personnel on site to evacuate the scene. Only after confirming that all personnel have evacuated the scene can they press the emergency start/stop button and the system will immediately implement the fire extinguishing operation; in the second case, when the gas fire extinguishing controller sends out an audible or visual alarm signal and is in the delay stage, if it is found that there is no fire alarm, the emergency start/stop button can be pressed immediately and the system will stop the fire extinguishing operation to avoid unnecessary losses.
3. System technical indicators:
1. System fire extinguishing method: total flooding, single-zone protection area: 20m2;
2. System nominal working pressure (20℃): 2.5MPa for level one,
3. System working pressure: 4.2MPa for level one,
4. System working pressure: 2.0MPa for level one,
5. Fire extinguishing agent filling density: ≤1120kg/m3 for level one;
6. Simulated starting bottle filling pressure (20℃): 4.0MPa;
7. Nozzle design working pressure: ≥0.6MPa for level one; Single nozzle protection radius R: When the nozzle installation height is <1.5m, R≤4.5m; When the nozzle installation height is >1.5m, R≤7.5m.
8. Nozzle protection height: installation height h≤6.5m; installation height h≥0.3m
9. The system has a delayed start function: delay 30S;
10. Fire extinguishing agent injection time: ≤10s;
11. Fire extinguishing system working environment temperature: 0℃~+50℃;
12. System start mode: automatic, electrical manual, mechanical emergency manual operation;
13. System start power supply: DC24V±3V, 1.1A;
14. Simulated fire extinguishing agent storage bottle specifications: 30L
15. Virtual simulation software for electrical installation of building and intelligent building Based on unity3d design, users can choose different interactive interface sizes according to computer configuration, and can choose six levels of image quality. The model in the software can be rotated 360°, enlarged, reduced, and translated. There are assistant prompts during the use of the software, the contents are as follows: A. Wet alarm system 1. System overview: Overview of the wet alarm system 2. Equipment awareness: It is equipped with the best viewing angle, equipment det*ls (displaying the introduction or parameters of the equipment), exercises (6 built-in multiple-choice questions, with prompts for correct and wrong choices), schematics (you can enter the device from the schematics). The equipment includes: sprinklers, water flow indicators, signal butterfly valves, exhaust valves, fire alarm controls, high-pressure pressure gauges, high-level water tanks, weiya control cabinets, pressure-stabilizing tanks, flow switches, end water testing devices, dr*nage facilities, water pump couplers, hydraulic alarms, timers, wet alarms, butterfly valves, check valves, fire pumps, safety pressure-stabilizing valves, and fire water tanks. 3. Principle display: Displays the working principle of the wet alarm system, 3D animation demonstrations, and 3D models
Translucent, you can see the internal water flow. Equipped with a practice module (4 built-in multiple-choice questions, both correct and wrong choices have prompts)
4. Design layout: There are multiple-choice questions and calculation questions, each question has a score, and the correct answer and score will be displayed after submission
B. Gas fire extinguishing system
1. System overview: Overview of gas fire extinguishing system
2. Equipment cognition: There are optimal viewing angles, equipment det*ls (displaying the introduction or parameters of the equipment), exercises (8 built-in multiple-choice questions, both correct and wrong choices have prompts), schematics (you can enter the equipment from the schematics). The equipment includes: nozzles, HFC-227 storage bottles, bottle head valves, heptafluoropropane check valves, high-pressure hoses, gas check valves, safety valves, weighing alarms, electromagnetic starters, selector valves, smoke alarms, and fire alarm controllers.
3. Principle display: Display the working principle of the gas fire extinguishing system, 3D animation demonstration, 3D model translucent, you can see the internal gas. Equipped with practice module (built-in 3 multiple-choice questions, with prompts for correct and wrong choices)
4. Design layout: There are 6 multiple-choice questions, each with scores, and the correct answer and score will be displayed after submission
C. Escape drill: Teaching in the form of fun games, escaping from the burning room within a limited time, and wrong choices will directly enter the score interface.
IV. Product specifications:
1. Working voltage: single-phase three-wire 220V±5% 50Hz
2. Machine capacity: <1500W
3. Dimensions: 2000×1000×1800cm3